B24 480kW Immersion Cooling System for Miners
System Overview:
- Capacity: Accommodates up to 96 Antminers or 120 Whatsminers.
- Cooling Performance: Delivers overclocked hashrate with a robust 480kW cooling capacity.
- Cooling Mechanism: Features a dual-loop circulation system with separate CDUs for optimal cooling.
- Infrastructure: Includes smart PDUs, comprehensive networking infrastructure, and integrated circulation pumps and piping.
- Cooling Options: Comes with a standard dry cooler, with an optional closed water cooling tower available.
- Design Benefits: High-density configuration, space-saving design, easy deployment, and remote management support.
480kW lmmersion System Specifications
Qty of B24 Tanks | 4 |
B24 Outer Size | 2486*746*530mm |
Input Voltage | 3-phase 350-480V 50/60Hz |
Output Voltage | Single-phase 200-277V 50/60Hz |
Cooling Capacity | 480kW@35°C |
Ambient Temp | -25°C ~ 55°C |
Net Weight (Tank) | 688kg |
Coolant Volume | 3000L |
Max Inlet/Outlet Temp | 45/65°C |
Max Power Load | 40kW |
Network | 100Mbps Ethernet switch |
Pipe Diameter | DN65/DN80 |
Dry Cooler | FHDC480 |
Dry Cooler (EC Fan) | |
Model | FHDC480 |
Cooling Capacity | 480kW |
Circulation Medium | Water/Glycol |
Input Voltage | 3-phase 350-480V 50/60Hz |
Max Power Load (kW) | 16 |
Max Inlet/Outlet Temp (°C) | 40/45 |
Reference Temperature (°C) | 35 |
Total Air Volume (m³/h) | 218543 |
Dimensions (mm) | 5250*1874*2100 |
Noise Level @25°C, 16m | 70 |
Shipping Weight (kg) | 2250 |
Operating Pressure (MPa) | 0.4 |
For most areas, the liquid cooling equipment will be shipped to you via sea freight. Ports and receiving points in different regions will incur different shipping charges. It is recommended that you contact customer service to confirm address details and calculate shipping costs before placing an order.