B24 1.2MW Immersion Cooling System – High-Efficiency Solution for Mining Operations
Key Features:
- Massive Capacity: Supports up to 240 Antminers or 300 Whatsminers with a 1.2MW cooling power for overclocked hashrate.
- Advanced Cooling: Features dual-loop circulation with separate CDUs for efficient temperature management.
- Integrated Design: Includes smart PDUs, networking, circulation pumps, and piping for a seamless setup.
- Flexible Cooling Options: Supports both dry cooler (default) and optional closed water cooling tower.
- Space-Saving: High-density design for efficient use of space.
- Easy Deployment: Simplified installation process with support for remote management.
Enhance your mining operations with the B24 1.2MW Immersion Cooling System, offering powerful cooling and integrated features for optimal performance.
1.2MW lmmersion System Specifications
Qty of B24 Tanks | 10 |
B24 Outer Size | 2486*746*530mm |
Input Voltage | 3-phase 350-480V 50/60Hz |
Output Voltage | Single-phase 200-277V 50/60Hz |
Cooling Capacity | 1.2MW@35°C |
Ambient Temp | -25°C ~ 55°C |
Net Weight (Tank) | 1720kg |
Coolant Volume | 7500L |
Max Inlet/Outlet Temp | 45/65°C |
Max Power Load | 90kW |
Network | 100Mbps Ethernet switch |
Pipe Diameter | DN65/DN150 |
Dry Cooler | FHDC1200 |
Dry Cooler (EC Fan) | |
Model | FHDC1200 |
Cooling Capacity | 1200kW |
Circulation Medium | Water/Glycol |
Input Voltage | 3-phase 350-480V 50/60Hz |
Max Power Load (kW) | 36 |
Max Inlet/Outlet Temp (°C) | 40/45 |
Reference Temperature (°C) | 35 |
Total Air Volume (m³/h) | 386826 |
Dimensions (mm) | 11250*1874*2100 |
Noise Level @25°C, 16m | 72 |
Shipping Weight (kg) | 4710 |
Operating Pressure (MPa) | 0.4 |
For most areas, the liquid cooling equipment will be shipped to you via sea freight. Ports and receiving points in different regions will incur different shipping charges. It is recommended that you contact customer service to confirm address details and calculate shipping costs before placing an order.